Quart de Poblet, Spain
Hotel | 137 sqm installation
| |
Description The installation is formed by 72 SOLAHART collectors, mod. L, situated in a suitable area. The 72 collectors are divided into 12 batteries of 6 collectors. The system uses a variable temperature control system which operates the primary and secundary circuits. The collector heat is transferred to the storage tank by an external heat exchanger. The variable temperature setting to start/stop the circulation pumps is 6 ºC. System use: ACS with a solar fraction of 80 %.
|
| Building
| Type of building | Hotel
| Number of users / dwellings, floors | 137 users 7 floors | Year of construction | 2005
| Total effective area (heated) | 192 m2 | Hot tap water consumption
| 3,395 m3/a (calculated)
| Whole energy consumption for heating purpose after CSTS implementation | 108,648 kWh/a | System engineering
| Year of construction of CSTS | 2006
| Type of collectors | Flat plate collectors
| Thermal power | 90 kWtherm.
| Aperture area of collectors*) | 130 m2 | Buffer storage | 12 m3 | Hot tap water storage | ./. | Total capacity of boilers with energy source | 155 + x kW, natural gas | Type of hot tap water heating | Centralised
| Type of heating system | Centralised
| Costs
| Total cost solar system | 59,913 Euro
| Cost of the CSTS / gross area of collectors | 416 Euro/m2 | Subsidies | 30 % | Output
| Output of solar heat**) | 79,158 kWh/a | Reduction of final energy***) | 113,083 kWh/a | CO2-emissions avoided | 26 CO2/a
| Solar performance guarantee | Yes
| *) Aperture area = light transmitting area of the front glass **) measured, between storage and piping to taps (solar system output) ***) related to the measured output mentioned before | |
| Owner
| INVERSORA DEL REINO DE VALENCIA | Operator (ESCo)
| ELECNOR, S.A. C/ Marqués de Mondéjar, 33 28028 Madrid, Spain Phone: +34 91 417 99 00 elecnor(at)elecnor.es www.elecnor.es
| |
Description of the CSTS
| Year of construction of CSTS | 2006
| Thermal power | 90 kWtherm. | Gross area of collectors | 144 m2 | Aperture area of collectors | 129.6 m2 | Type of collectors | Flat plate collectors
| Type of assembly | On flat roof
| Orientation of collectors | South (0°) | Inclination angle to horizon | 45 °
| Freezing protection | Glycol
| Overheating protection | Expansion vessel
| Operation mode | Low flow
| Use of CSTS for | Hot tap water heating
| Buffer storage | 12 m3 (3 × 4 m3)
| Hot tap water storage | ./. | Control of backup-system / CSTS | Shared control
| Hot tap water system
| Type of hot water heating | Centralised
| Recirculation system | Yes
| For decentralised systems: The installation on the consumer site | ./.
| Size of storage for hot tap water | not available | Specification (if necessary) | Separated back-up heater/boiler for hot water heating only: standard, natural gas, 2004, capacity not available | Space heating system
| Type of heating system | Centralised
| Number of boilers | 1
| Total capacity (power output) of boilers | 155 kW | Capacity of each boiler (year of construction) | No. 1: 155 kW (2005)
| Energy source | Natural gas
| Type of boiler system | Standard
| Type of operation
| Operator of the CSTS system | ESCo
| CSTS monitoring | Yes: The output of solar heat. The ESCO supervises the data. | Data accessible via internet | No
| Scientific monitoring / follow up | No
| Maintenance contract | Yes: one to three times a year
| Visualisation of the solar heat output | Yes
| Yield of CSTS plant
| Output of solar heat | 79,158 kWh/a | Origin of data | Design (calculated)
| Measuring point | not available
| Reduction of final energy | 113,083 kWh/a | Origin of data | Designed data
| Solar performance guarantee | Yes
| Heat consumption
| Whole energy consumption for heating purposes after CSTS implementation | 108,648 kWh/a | Origin of data | not available
| Energy used for | Hot tap water heating
| Whole energy consumption for heating purposes before CSTS implementation | 221,731 kWh/a
| Total tap water consumption | not available
| Hot tap water consumption | 3,395 m3/a | Hot tap water temperature | 45 °C | Cold water temperature | 12.3 °C | | Summary
| The installation is formed by 72 SOLAHART collectors, mod. L, situated in a suitable area. The 72 collectors are divided into 12 batteries of 6 collectors. The system uses a variable temperature control system which operates the primary and secundary circuits.
The collector heat is transferred to the storage tank by an external heat exchanger. The variable temperature setting to start/stop the circulation pumps is 6 ºC.
System use: ACS with a solar fraction of 80%.
| | Installer
| SACLIMA S.L. Elena Salazar Mir Pol. Ind. "Els Mollons C/Torners, 21 46970 Alaquas (Valencia), Spain Phone: +34 96 151 61 62 Fax: +34 96 151 22 88 info(at)saclima.com www.saclima.es |
Collectors' manufacturer
| Solarhart industries Rob meesters Vlamoven weg 12 5708JV Helmond, Netherlands Phone: +31 492579696 Fax: +31 492579694 r.meesters(at)solahart-europe.com www.solahart.com | |
Financing of the CSTS
| Form of financing | Purchase
| Distribution in percentage | 20 % loans 30 % subsidies (granted by the Valencia Energy Agency)
| Costs of solar materials
| Total cost of solar system | 59,913 Euro | Detailed costs for
| | Collectors
| 34,710 Euro | Elevation / mounting structure
| 4,692 Euro | Storage / heat exchanger
| 16,890 Euro | Backup heater
| ./. | Control
| 888 Euro | Installation
| ./. | Planning / Engineering
| ./. | Others (system of pumping)
| 2,750 Euro | Operation costs of heating system
| Increase of the operation cost after CSTS implementation | not available
| | |
|
Experiences management
| Experienced problems or failures? | No
| Found solutions to these problems or failures? | ./.
| Financial effects / project performance
| Project economically efficient? | Yes
| Fiscal or other financial effects? | No
| Effects on rental fees? | No
| Experiences technical staff
| Experienced problems or failures? | No
| Found solutions to these problems or failures? | ./.
| |
The owner of the hotel was interested in solar system, he knew all the costs, the investment and the savings were calculated.
The director of the Hotel contacted the installer and the technical department of SACLIMA designed the installation and provided the solar system.
The installation is working right.
|